Room cooling (CRAC)

Room precision cooling: Datacool & Cyber Master

Room-level precision air conditioning holding temperature to ±1 °C and relative humidity to ±5%, in DX air-cooled, water-cooled and chilled-water configurations from 7.5 kW to 177.2 kW, for rooms that run 24 hours a day, 365 days a year.

Overview

What this range delivers

The Datacool Series covers more than ten cooling configurations, from air-cooled and water-cooled DX to chilled water, dual-cool and glycol free-cooling, with EER of 3.0 and above. Every unit pairs EC fans, PTC reheat and electrode humidification with a 7-inch touch screen and RS485 Modbus control.

±1 °C / ±5% RH

Constant temperature and humidity control for precision environments, with set ranges of 15 to 35 °C and 30 to 80% RH.

10+ cooling configurations

Air-cooled, water-cooled, glycol, chilled water, double coil, CW+DX dual cool and free cooling variants from one platform.

Scroll + EC technology

Flexible scroll compressors (EC option modulating 10 to 100%) and backward-inclined EC fans with 20 to 300 Pa ESP.

Protection & monitoring

Phase-sequence, over/under-voltage and phase-loss protection as standard; RS485 Modbus RTU standard, SNMP/HTTP and web access optional, 1000 alarm records.

The range

Datacool Series: three cooling technologies

DX · air-cooled

Datacool DX air-cooled

SA30 to DA120 up/down-flow units from 32.5 to 122.9 kW with matched air-cooled condensers, single or dual refrigerant circuits, R410A.

DX · water-cooled

Datacool water-cooled

SW30 to DW120 units from 29.3 kW with water-side condensing (rated 30/35 °C in/out water), for sites where outdoor condensers are impractical.

Chilled water

Datacool chilled-water

SC30 to DC150 units from 38.2 kW (SC30) up to 177.2 kW (DC140) at 7/12 °C water, with EC/AC fans and 2-way valves as standard.

Selected models

Datacool DX air-cooled: representative models

ParameterSA30SA50DA65DA90DA120
Total cooling capacity32.5 kW50.0 kW65.1 kW92.1 kW122.9 kW
Sensible capacity29.3 kW45.0 kW58.8 kW83.6 kW105.2 kW
Refrigerant circuitsSingleSingleDualDualDual
Air volume8325 m³/h12,400 m³/h16,650 m³/h22,600 m³/h27,100 m³/h
Reheat (PTC)6 kW9 kW9 kW12 kW12 kW
Humidifier (electrode)8 kg/h10 kg/h10 kg/h12 kg/h12 kg/h
RefrigerantR410AR410AR410AR410AR410A
FilterG4G4G4G4G4
W × D × H1126 × 990 × 1975 mm1326 × 990 × 1975 mm1826 × 990 × 1975 mm2226 × 990 × 1975 mm2426 × 990 × 1975 mm
Weight433 kg528 kg688 kg866 kg980 kg
Companion series

Cyber Master Series: per-model detail

ParameterFO-CYAS30FO-CYAD90FO-CYAS50FO-CYAD65FO-CYAD120
Cooling typeDX, air-cooledDX, air-cooledChilled waterChilled waterChilled water
Total cooling capacity13.7 kW61.2 kW32.8 kW48.1 kW93.3 kW
Sensible capacity12.3 kW55.1 kW30.1 kW43.8 kW85.2 kW
Air volume3600 m³/h26,200 m³/h11,600 m³/h16,400 m³/h32,800 m³/h
Supply air flowUp front flowDown flowDown flowDown flowDown flow
Reheat (PTC)3 kW9 kW6 kW9 kW12 kW
Humidifier (electrode)3 kg/h15 kg/h8 kg/h8 kg/h8 kg/h
MonitoringRS485, SNMP (optional)RS485, SNMP (optional)RS485, SNMP (optional)RS485, BACnetRS485, SNMP (optional)
Indoor unit (W × D × H)650 × 550 × 1850 mm2226 × 990 × 1975 mm925 × 990 × 1975 mm1675 × 990 × 1975 mm2725 × 990 × 1975 mm
Weight188 kg768 kg352 kg520 kg850 kg
Inside the unit

Ten components engineered for continuous duty

  • Flexible scroll compressor · High efficiency, with an EC option modulating cooling output from 10 to 100% of capacity.
  • EC fans · Backward-inclined, continuously adjustable airflow with low noise and low energy use.
  • Electronic expansion valve · Precision refrigerant control from internationally proven brands.
  • Electrode humidifier · Runs on tap water, self-cleaning, produces pure steam and is serviceable without stopping the unit.
  • Three-stage PTC heater · Perfect overheat protection and air-ionization prevention.
  • Hydrophilic-fin evaporator · Internally threaded copper tubes, corrosion-resistant and matched to the refrigeration circuit.
  • 7-inch touch control · Status, alarms, temperature and humidity curves, component run-times and 1000 historical alarm records.
Applications

Where room precision cooling is deployed

Data centers
Telecom switch rooms
Labs & precision rooms
UPS & battery rooms

Scope your Room Precision Cooling

Share your heat load, site and redundancy requirements. Our engineers respond with a tailored cooling configuration.

Request a Quote