Tower UPS
A standalone online double-conversion tower UPS from 1 kVA single-phase to 500 kVA three-phase, engineered to VFI-SS-111 with 0 ms transfer, high efficiency and parallel expansion for enterprise rooms, telecom sites and data-center loads.
Key applications: data-center and server rooms, telecom and network sites, banking and enterprise, healthcare.
Why Tower UPS
Online double-conversion
Pure online (VFI) topology to VFI-SS-111 with 0 ms transfer between mains, battery and bypass for clean, uninterrupted output.
1 kVA to 500 kVA
Single-phase 1–10 kVA and three-phase 10–500 kVA units cover everything from a comms room to a data hall.
Parallel & expandable
Parallel operation of up to 6 units with shared battery banks and LBS synchronization for capacity and redundancy.
High efficiency
Up to 96% online efficiency and ECO mode up to 99%, with input power factor >0.99 and current THD <3%.
Capacity line-up
| Model | Rated capacity | Phase |
|---|---|---|
| FO-TUPS-1101 | 1 kVA / 1 kW | Single-phase |
| FO-TUPS-1103 | 3 kVA / 3 kW | Single-phase |
| FO-TUPS-1106 | 6 kVA / 6 kW | Single-phase |
| FO-TUPS-1110 | 10 kVA / 10 kW | Single-phase |
| FO-TUPS-3310 | 10 kVA / 10 kW | Three-phase |
| FO-TUPS-33030 | 30 kVA / 30 kW | Three-phase |
| FO-TUPS-3350 | 50 kVA / 50 kW | Three-phase |
| FO-TUPS-33060 | 60 kVA / 60 kW | Three-phase |
| FO-TUPS-33100 | 100 kVA / 100 kW | Three-phase |
| FO-TUPS-33200 | 200 kVA / 200 kW | Three-phase |
| FO-TUPS-33300 | 300 kVA / 300 kW | Three-phase |
| FO-TUPS-33500 | 500 kVA / 500 kW | Three-phase |
Additional ratings (2, 15, 20, 40, 80, 120, 150, 250, 400 kVA) and long-backup versions are available; high-frequency (unity PF) and transformer-based configurations are selected per project.
System & electrical
| Parameter | Value |
|---|---|
| Topology | Online double-conversion (VFI-SS-111) |
| Input voltage | 380 / 400 / 415 VAC (3-phase); 220 / 230 / 240 VAC (single-phase) |
| Input voltage range | 285–520 VAC (3-phase, full load) |
| Input frequency | 40–70 Hz |
| Input power factor | >0.99 |
| Input current THD | <3% |
| Output voltage | 380 / 400 / 415 VAC (3-phase); 220 / 230 / 240 VAC (single-phase) |
| Output frequency | 50 / 60 Hz |
| Output voltage accuracy | ±1% |
| Output THD | ≤1% (linear load), ≤3% (non-linear load) |
| Output power factor | 1.0 (unity; 0.9 on LF variants) |
| Transfer time | 0 ms (mains ↔ battery, inverter ↔ bypass) |
| System efficiency | Up to 96% (online); up to 99% (ECO mode) |
| Overload capacity | 110% for 60 min; 125% for 10 min; 150% for 1 min |
| Parallel operation | Up to 6 units, shared battery, LBS synchronization |
| Battery | 12 V blocks: 2–8, 16–20 or 32–44 cells; VRLA or LiFePO4 |
| Display | LCD + LED colour touch screen |
| Communication | RS232, RS485, dry contact, SNMP (optional), EPO |
| Protection level | IP20 |
| Operating temperature | 0°C to 40°C |
| Relative humidity | 0–95% non-condensing |
| MTBF | >200,000 h |
Specifications reflect the FIBER OCEAN FO-TUPS datasheet. Exact ratings vary by model; regional configuration and options are confirmed per project.